SR-611 Air conditioning system with chamber Educational Equipment Thermal Transfer Experiment Equipment for college, vocational training center, university. 

SR-611 Air conditioning system with chamber Educational Equipment Thermal Transfer Experiment Equipment

Description

Comfort is of great importance in the air conditioning of rooms and buildings. The comfort depends on the temperature, the relative humidity and the flow velocity of the air. According to DIN 13779 a so-called “comfort zone” has been defined which specifies the values an air conditioning system should achieve.

 

SR 611 is a full air conditioning system with comprehensive test options. The effect of the air humidity and temperature on the comfort is examined. The system has a climatic chamber designed for test persons to be inside. This allows the trainee to study the effect of different system operating states on his own well-being. The components used, such as radial fan, electric air heater, steam humidifier and water chiller are all used in commercial air conditioning and ventilation technology. A PLC air conditioning controller monitors and controls all functions. In addition to the automatic operation it also enables the manual operation of the system.

 

Sensors record air humidity, temperature, power, flow rate, and flow velocity. The measured values can be read on digital displays. At the same time, the measured values can also be transmitted directly to a PC via USB. The data acquisition software is included.

2.Technical details

Specification

air conditioning system with chamber for conditioning and air technology investigations

chamber suitable for test persons to be inside

PLC air conditioning controller, manual and automatic operation

industrial components: fans, air-cooled water chiller, air cooler, air heater, steam humidifier

digital displays for air temperature, air humidity, air velocity, temperature of the cold water, power

 

Technical data

PLC air conditioning controller

17 universal inputs, 4 analogue outputs, 10 switching outputs

Radial fan

power consumption: 0,75kW

max. flow rate: 39m3/min

pressure difference: 450Pa

Air heater: 6x 250W

Steam humidifier

steam capacity: 6kg/h

power consumption: 4,5kW

Water chiller

power consumption: 2,1kW

refrigeration capacity: 6,2kW at 32°C, ΔT=5K

fan, volumetric air flow rate: 3500m3/h

Air cooler, capacity: 4,84kW

Refrigerant

AR410A, GWP: 2088, filling volume: 1,3kg, ACO2-equivalent: 2,7t

 

Measuring ranges

flow rate: 0…1500L/h (water)

temperature: 7x 0…50°C (air), 2x 0…50°C (water)

humidity: 7x 10…90%

flow velocity: 2x 0…20m/s (air)

power: 2x 0…6kW, 2x 0…1,5kW

 

400V, 50Hz, 3 phases

400V, 60Hz, 3 phases; 230V, 60Hz, 3 phases

UL/CSA optional

 

Required for operation